Residual Current Device with Overcurrent Protection (RCDO) from Schrack, series B, is designed to protect electrical circuits from leakage currents and overloads. The device combines differential circuit breaker functionality and overcurrent protection in a single enclosure.
Key Parameters:
- Rated Current: 25A
- Pole Configuration: 1+N (single-phase with neutral)
- Rated Sensitivity (IΔn): 30mA
- Time-Current Characteristic: B (fast-acting)
- Response Type: A (sensitive to sinusoidal and pulsating direct current)
- Breaking Capacity: 6kA
- Tripping Time: instantaneous
Technical Specifications:
- Power Loss: 4.80W
- Operating Temperature Range: -35°C to +60°C
- Dimensions: 75.10 × 35.00 × 80.00 mm
- Weight: 0.25 kg
- Compliance Standards: EN 61009-1:2012 + A12:2006, EN 61009-2-1:1994 + A11:1998
- Packaging: 1 pc.
- EAN Code: 9004840506624
The device provides reliable protection against direct and indirect contact with conductors, as well as against ground faults in single-phase AC networks.
| EAN Code | 9004840506624 |
|---|---|
| Net Length | 75.10mm |
| Net Width | 35.00mm |
| Net Height | 80.00mm |
| Net Weight | 0.25kg |
| Power Loss | 4.80W |
| Min. Ambient Temperature | -35°C |
| Max. Ambient Temperature | 60°C |
| Standards | EN 61009-1:2012 + A12:2006, EN 61009-2-1:1994 + A11:1998 |
| Type | A (sensitive to pulsating direct current) |
| Type | instantaneous |
| Rated Sensitivity IΔn | 30mA |
| Characteristic | B |
| Current Rating | 25A |
| Poles | 1+N |
| Breaking Capacity | 6kA |
| Series | BOLF |
| Manufacturer | Schrack |
| Packaging | 1 pc. |